Morangup Power cycle issues on Hot Days — A Community Notice

Why Morangup Power “Flickers” on Hot Afternoons (and why it’s often ~30 seconds)

Published: Thursday, 22 January 2026  •  Area: Morangup / Greater Eastern Hills (WA)

If your power drops out briefly on a very hot afternoon and then comes back by itself about half a minute later, you’re most likely seeing a network protection device doing its job — not “random faults” inside your house. Morangup Residents Group — Community explainer

What residents are noticing

On extreme heat days (often still close to 40°C near late afternoon), some parts of Morangup can experience short, repeat interruptions — commonly around 20–40 seconds — while other roads remain unaffected. The pattern many people report is that it happens right when households arrive home and switch on high-load appliances: air-conditioning, ovens, cooktops, hot-water boosts, pumps, workshops, etc.

The simple explanation

Morangup is supplied via a rural distribution network with multiple branches. During the hottest part of the day, the network is already under stress from heat. Then, when many homes switch on cooling and cooking at the same time, the supply can hit a practical limit on a particular branch of the feeder.

The network protection system reacts by opening (turning off) that section briefly, then automatically restoring it — which is why it can look like a “trip” that self-resets.

Why it happens right when people switch things on

Air-conditioners are the big one. Many modern systems draw a large current when they first start. This is called start-up / inrush current. If a lot of systems start within the same few minutes on the same local supply branch, the surge can briefly look like a fault condition to upstream protection devices.

Why it’s often about 30 seconds

Those upstream devices (often called auto-reclosers) are designed for overhead rural networks. Their job is to open the circuit when a problem is detected, pause for a preset interval (the “dead time”), then reclose automatically if the fault was only temporary.

A ~30 second gap is a very common “slow reclose” setting that gives time for the surge to pass, motors to settle, and the network to stabilise.

Why some roads drop and others don’t

This is the key point: Morangup’s network is not one single pipe. It’s a tree of feeders and branches. Neighbours can be on different branches, different transformers, or even different phases.

Pros and cons of the “auto-reclose” behaviour

Pros
Cons

What to expect on very hot days

If the pattern is peak-load related, the risk window is commonly late afternoon into early evening (roughly when households return home and cooling/cooking ramps up). It may ease later at night once outdoor temperatures drop and demand spreads out.

Quick “what can I do right now?” checklist

  • Stagger start-ups: if you have multiple air-cons, avoid starting them at the exact same time.
  • Pre-cool earlier: start cooling before peak time (mid-afternoon) so compressors don’t all slam on at once.
  • Ease the set-point: 24–26°C can reduce compressor cycling and peak draw.
  • Avoid stacking loads: don’t start oven + dryer + workshop + hot-water boost all together at 5pm.
  • Protect electronics: consider a small UPS for modem/router so internet stays up during the 30s dip.

Community-level ways to minimise the impact

No one household “causes” it. It’s a coincidence issue: lots of homes switching on heavy loads at the same time on a rural feeder. The best community impacts come from smoothing the peaks.

What about “getting 3-phase”?

Before anyone asks: 3-phase is not an easy switch in rural areas. It is not just a paperwork change. It can require network upgrades (poles, conductors, balancing), transformer capacity, and a suitable service run.

Also: 3-phase doesn’t magically reduce total energy use. It mainly spreads large loads more evenly across phases. If the whole branch is near capacity, upgrades are still upgrades. Plain-English note for rural networks

FAQ

Is this an issue inside my house?

If the whole street/pocket goes off then returns about half a minute later, it’s usually upstream network behaviour. If only your house trips, that can be a private wiring issue (main switch, RCD, appliance fault).

Why does it happen more on 40°C days?

Heat drives demand and increases stress on lines and equipment. Peak demand coincides with people arriving home, cooking, and pushing cooling harder.

Why do battery homes say “we’re fine”?

If you’re running from batteries (or exporting solar), your home can ride through a short dip. You’re also drawing less from the local feeder, which helps the broader supply.

Is it “grid overload”?

“Overload” is a loose word people use. The more accurate idea is: peak coincident demand on a specific feeder branch exceeds what that section can comfortably support (current, voltage stability, and protection thresholds).

What should I do if it keeps happening?

Community note: This article is a plain-English explainer based on common rural distribution behaviour and observed local patterns. For faults, danger, fallen lines, or urgent electrical hazards, always follow official channels and emergency advice.